Page 1 - Superior Ci

Superior CiInstallation, Servicing & User InstructionsGB

Page 2 - Installer checklist

3.1 UNPACKING THE BOILERThe standard appliance is supplied in two cardboard carton.In addition up to two extension duct kits may be used. If theappl

Page 3

3.5. FLUE AND TERMINAL INSTALLATION3.5.1 Coaxial duct diaphragmThe boiler is supplied with diaphragm to be used in relationto the maximum horizontal

Page 4 - *Factory setting

10Fig. 10REAR FLUE OUTLETR.H. SIDE FLUE OUTLETL.H. SIDE FLUE OUTLETTelescopic flueTABLE 8 - Maximum flue lengths (measured from appliance casing to ou

Page 5

11– Remove the turret from the flue assembly.– From outside the building, slide the duct assembly into thewall until the sealing ring forms a g

Page 6

123.8.2 Schematic system wiring diagramsFig. 14FULLY PUMPED SYSTEM USING TWO ZONE VALVES

Page 7

13Fig. 15FULLY PUMPED SYSTEM USING MID POSITION ZONE VALVE

Page 8

14SIME SUPPORT THE BENCHMARK INITIATIVEAll relevant sections of the logbook must be filled in at thetime of installation and thereafter servi

Page 9

15To ensure continued efficient operation of the appliance, it isrecommended that it is checked and serviced as necessaryat regular intervals. The f

Page 10 - 3 INSTALLING THE BOILER

16If an electrical fault occurs on the appliance the preliminaryelectrical system checks contained in the British Gas Multi-meter Instruct

Page 11

176.5 FAULT FINDINGBefore proceeding through this fault finding guide:1) ensure all connections to the electronic circuit boardand the 12 way c

Page 12 - L.H. SIDE FLUE OUTLET

Please refer to commissioning instructions for filling in the log bookNote: All CORGI registered installers carry a CORGI ID Card. You can check your

Page 13

187 WIRING DIAGRAM AND INTERNAL VIEW7.1 FUNCTIONAL FLOW WIRING DIAGRAMKEYL PhaseN NeutralF Fuse F2AEA Ignition electrodeER Ionisation probeA Control b

Page 14

1934 6718529161011121314157.2 INTERNAL VIEWFig. 19KEY1 Igniter P.CB.2 Safety stat 105°C3 Air pressure switch4 Positive pressure test point5 Negative p

Page 15

Before commencing any service operation, ISOLATE themains electrical supply, and TURN OFF the gas supply at themain service cock. It is the law

Page 16 - 4 COMMISSIONING AND TESTING

21box, taking note of their respective position.– Slide the burner forwards and at the same time feed thetwo wires through the grommet in the

Page 17

229 SHORT LIST OF PARTS13452678911121013Fig. 22KEY G.C. PART NO DESCRIPTION NO OFF MAKER’S PT NO1 Main Burner 40-50-60 1 51898011 Main Burner 80 1 518

Page 18 - 6 FAULT FINDING

23USER INSTRUCTIONSVERY IMPORTANT!PLEASE MAKE SURE YOUR LOG BOOK ENCLOSED IS FILLED IN CORRECTLY.ALL CORGI REGISTERED INSTALLERS CARRY A CORGI ID CARD

Page 19

trol.– Turn on the gas supply.– Turn the boiler control on, and to maximum. Check theboiler lights.– Set the boiler control to the required t

Page 21 - 7.2 INTERNAL VIEW

Cod. 6274224 - Documentation Dpt.heating products u.k.ltd.Jubilee Works - Middlecroft Road - Staveley - Chesterfield - Derbyshire S 43 3XN Tel. 01246

Page 22 - 8 REPLACEMENT OF PARTS

1.1 INTRODUCTIONThe Sime “SUPERIOR Ci” is a range of wall mounted cast ironboilers. The combustion system is fan assisted and has asmall bala

Page 23 - 3,5 ±0,5

21.3 GENERAL DATATABLE 3a - Nominal boiler ratings (2 minutes after lighting) for Superior 40 CiMODE OUTPUT INPUT (N.C.V.) INPUT (G.C.V.) BURNER PRES

Page 24 - 9 SHORT LIST OF PARTS

340 Ci 50 Ci 60 Ci 80 CiBurner Injector 1ø mm 3.25 3.25 3.55 4.10Max. gas consumpt.m3/h1,38 1,69 2,05 2,75System Press min bar 0.12max bar 3Adjustable

Page 25 - USER INSTRUCTIONS

2.1 STATUTORY REQUIREMENTSGAS SAFETY [INSTALLATION AND USE REGULATIONS [asamended]. It is the law that a registered person, in accordan-ce with

Page 26

by a purpose designed guard. Terminal guards are availablefrom Quinnell, Barrett, and Quinnell, Old Kent Road, London.State the model C2, [G.C.

Page 27

priate to one of these methods. The system pressure mustnot be less than the static head of the system.A safety valve set at 3 bar must be fitted to t

Page 28

7TYPICAL SYSTEM DESIGN, FULLY PUMPED, OPEN VENTED.Fig. 5